ACTFLEX 900R pack
● TDS-900R · Rev 3 · 2 October 2026

ACTFLEX 900R Butyl sheet membrane

Dual-fabric butyl rubber internal undertile sheet membrane, heat-welded laps

Internal wet area butyl sheet. Tile or screed from 1 hour after installation.

0.9 mm gaugeInternal onlyCover after 1 h
0.9 mmGauge
1.4 m x 20 mRoll size
≈ 25–26 m²Coverage
40 mm minLaps
1 hourCover from
24 hoursFlood test
● The numbers

ACTFLEX 900R coverage, coats and cure times

Dual-fabric butyl rubber sheet for showers, bathrooms, ensuites and laundries. It is bonded with water-based ACTFLEX 302 ADHESIVE and its laps are hot-air welded.

Gauge
0.9 mmtotal, white nonwoven fabric on both faces · TDS p3
Roll size
1.4 m x 20 m28 m² gross · TDS p3
Coverage
≈ 25–26 m²practical per roll; 27.2 m² effective after side laps · TDS p9
Laps
40 mm minside and end laps, hot-air welded · TDS p6
Cover from
1 hourtile, screed or flood test, after installation · TDS p10
Flood test
24 hours50 mm minimum depth at the highest point · TDS p10
Apply at
5–35°Cambient (average) · TDS p3
Adhesive
8–10 m²/LACTFLEX 302 ADHESIVE, per coated face · TDS p3
Upturn
150 mm minfloor sheet above finished floor, over solid backing · TDS p7

From the FORSPEC data sheet, TDS-900R · Revision 3 · 2 October 2026. Times are at 25°C and 50% relative humidity unless the data sheet says otherwise.

● Real jobs

ACTFLEX 900R on site

A sheet floor in 3 hours
The pipe penetration detail

More FORSPEC jobs

● Is it right for the job

Where ACTFLEX 900R is used

Use it for

  • Showers, bathrooms, ensuites and laundries
  • Under direct-stick tiling on the upper fabric face
  • Under bonded screeds
  • Over existing cured screeds, primed with two coats of ACTFLEX EP250
  • Wet areas with fully encapsulated electric underfloor heating
  • Hybrid walls and terminations with ACTFLEX 906 WPU or 989 CWP

Know before you start

  • Internal only: not for external, below-grade or UV-exposed areas, use ACTFLEX 1300R
  • Not a wearing surface: always cover with tiles, screed or a protective finish
  • Heating cables must never sit directly against the membrane underside
  • Not below 5°C or above 35°C ambient
● On site

How to apply ACTFLEX 900R

  1. 01

    Prepare

    Clean, sound, dry and vacuumed. New concrete cured 28 days. Falls 1:80 to 1:50 to the waste. Pack out gaps so the 150 mm floor upturn is solidly supported.

  2. 02

    Prime if needed

    No primer on sound, dry substrates. Two coats of ACTFLEX EP250 over an existing screed or where moisture is above 80% RH or 15 g/m²/24 h.

  3. 03

    Bond the floor

    ACTFLEX 302 ADHESIVE on both faces at 8–10 m²/L per face. Let both go tacky, bed the sheet from one edge, roll it, and run it 150 mm up every wall.

  4. 04

    Detail

    Form corners, penetrations and the floor waste from cut strips (200–300 mm wide) or ACTFLEX SA TAPE. Weld every detail to the sheet and probe each weld.

  5. 05

    Walls

    Wall sheets lapped 40 mm over the floor upturn and welded, to 1800 mm or 50 mm above the shower rose, whichever is greater. Or use ACTFLEX 906 WPU or 989 CWP.

  6. 06

    Test and cover

    Probe every seam, then flood test from 1 hour after installation: 50 mm deep for 24 hours. Tile or screed after the test passes.

A short guide from the data sheet. Read the full ACTFLEX 900R TDS before you start.

● Proof

ACTFLEX 900R test reports and compliance

AS/NZS 4858:2004
Designed and manufactured to complyManufacturer classification
AS 3740:2021
Details comply: 150 mm upturns, 1800 mm shower wallsFalls 1:80 to 1:50 to waste
AS 3558.1
Water absorption 2.0% maximumTypical R&D value
EN 12316-2 / 12317-2
Weld strength determined to these methodsCertified values to follow
AS/NZS 4020
Not certifiedWritten FORSPEC confirmation needed

Results as stated in the data sheet, TDS-900R · Revision 3 · 2 October 2026. Warranty up to 25 years, depending on the system: ask FORSPEC which term applies to your system.

● Questions

ACTFLEX 900R questions

How much ACTFLEX 900R do I need?

A roll is 1.4 m x 20 m, 28 m² gross. Practical coverage is about 25–26 m² per roll. Allow for 150 mm floor upturns, wall sheets to 1800 mm, detail strips and about 10% wastage.

When can I tile over ACTFLEX 900R?

From 1 hour after installation, direct onto the fabric face with ACTFLEX BIOSET or a compatible cement-based tile adhesive. No primer or abrasion is needed. Flood test before tiling.

Do I need a primer?

Not on sound, dry internal substrates. Two coats of ACTFLEX EP250 are needed over an existing screed, or where moisture is above 80% RH or 15 g/m²/24 h.

Can it go over underfloor heating?

Yes, if the cables are fully encapsulated in a FORSPEC screed or levelling compound beneath the membrane. Cables must never sit directly against the membrane underside.

Can I use it outside?

No. ACTFLEX 900R is internal only. For external, below-grade or UV-exposed areas use ACTFLEX 1300R, or ask FORSPEC Technical Services.

Which adhesive does it use?

ACTFLEX 302 ADHESIVE, a water-based, low-odour contact adhesive with water clean-up. ACTFLEX 301 ADHESIVE (solvent-based) is an approved alternative in well-ventilated areas only.

● Documents

ACTFLEX 900R TDS and SDS

Always work from the current data sheet. Every FORSPEC TDS and SDS →