AS 4654 Parts 1 and 2. Balcony and roof membranes.
·4 min read·FORSPEC Technical Team
The short version
- AS 4654.1 is the membrane: the tests it passes, matched to an exposed or a covered job.
- AS 4654.2 is the job: falls, fillets, upturns, terminations, outlets and what goes on top.
- Many well-known figures (upturn heights, 1 in 100, 8% moisture, a 50 mm screed) are guide figures, not requirements.
AS 4654 covers membranes outside and above ground: balconies, roofs, podiums. It comes in two parts. Both are 2012 editions, and NCC 2025 still calls up those editions.
Part 1: the membrane
- Part 2 has every system designed as exposed or covered. The membrane has to pass the Part 1 tests that match: UV resistance for an exposed membrane, abrasion for one that will be walked on.
- The membrane is classed by how far it stretches before it breaks: Class I under 60%, Class II 60 to 299%, Class III 300% or more.
- Part 2 then asks for the materials to meet Part 1 and for the system to suit its service conditions.
A test report to AS 4654.1 shows the membrane passed those tests. It does not show the balcony was built right. That is Part 2.
Part 2: the job
- Substrate
- No particleboard outside. A roof tile underlay is not a membrane.
- Falls
- Water reaches the outlet with none left standing.
- Fillets
- At every change of plane.
- Upturns
- High enough above the finished surface that water, wind-driven water included, cannot get over. The requirement gives no number.
- Terminations
- Over-flashing let into a reglet of at least 15 mm and lapped at least 75 mm. Pressure-seal fixings at 150 mm centres or closer.
- Doors
- The flashing under the sill is part of the membrane system.
- Joints
- At a structural joint the membrane stops, or runs over it unbonded for 100 mm.
- Outlets
- The membrane turns down into the outlet or is fixed to a flange. Every drain has a grate, sump or cage.
- Planters
- The membrane is sealed to the outlet and taken at least 100 mm above the soil.
- Protection
- The membrane is protected until it is covered, unless it is an exposed system made to be walked on.
Guide figures, not requirements
Many of the AS 4654.2 numbers people quote sit in notes or in the informative Appendix A. They are good practice and a designer can lean on them, but the standard does not require them.
- Upturn heights by site wind class: see balcony upturn height.
- A fall of 1 in 100. On concrete for apartment and commercial buildings, NCC 2025 asks for 1:80 in the structural slab.
- Fillets of 40 × 40 mm for a sheet and 15 × 15 mm for a liquid membrane.
- 8% on a moisture meter before the membrane: see what 8% really means.
- At least 50 mm, with light mesh, for an unbonded screed over the membrane. Under tiles, the tiling standard AS 3958 sets its own minimum as a requirement: see screed thickness.
- A 24-hour water test: see flood testing a membrane.
What NCC 2025 adds
The standard itself has not changed since 2012. What changed is the layer on top. For concrete balconies, roofs and podiums on apartment and commercial buildings, NCC 2025 asks for a fall of at least 1:80 in the structural slab itself (a screed or tile bed does not count, except in planters), the membrane laid straight on the slab, and a finish that either drains down to the membrane or is fixed straight to it. It also adds rules for set-downs at doors, hobs at edges, overflows and where joints sit. When it starts depends on the state: see NCC 2025 waterproofing changes.
The 70 mm set-down in NCC 2025 is a step in the concrete, not the membrane height. The AS 4654.2 upturn is still measured from the finished surface.
Where AS 4654 stops
- Below ground. Basements and tanking are outside it, and no Australian Standard covers them: see is there a basement waterproofing standard?
- Pools. Outside it too.
- Tiles. AS 4654.2 does not test how a tile adhesive holds to the membrane. The tiling standard, AS 3958, asks for more under tiles: the AS ISO 13007.5 test (liquid) or the AS 13007.6 test (sheet), and an adhesive tested with that membrane.
Where this comes from
- AS 4654.1-2012: 2.2, 2.3, 2.7; App A
- AS 4654.2-2012: 1.5, 1.6, 2.4.1, 2.5.1, 2.5.2, 2.7, 2.8.1.1, 2.8.1.3, 2.8.3, 2.9, 2.10, 2.13, 2.14, notes; App A
- AS 3958:2023: 2.14
- NCC 2025 Volume One: F1D4, F1D6, F1D7, F1D10
Standards are summarised in FORSPEC's own words as a guide. Read the standard itself and your project documents before you build.
General information, correct at the date shown. Not advice for your job.
Systems, products and drawings
Got a job this applies to?
Send the drawings or a few photos. FORSPEC comes back with the system, the details and the products for your job, within 6 business hours.