The short version

  • The puddle flange (the standard calls it a leak control flange) is an AS 3740 requirement, not a plumbing code one.
  • It must be recessed into the floor, sealed to the pipe, fixed so it cannot move and the same size as the riser.
  • The membrane is bonded onto the flange. If the flange sits proud or loose, the membrane cannot do its job.
FORSPEC standard detail EEL007: roof outlet with a rubber puddle flange recessed flush, liquid membrane lapped onto the flange and down into the outlet
Detail EEL007: the flange recessed flush and the membrane taken onto it and into the outlet.

Watch the explainer

Explainer video: Puddle flanges: the five rules at the floor waste

Water that gets under the tiles runs along the membrane to the waste. The puddle flange is the part that lets it into the pipe. Get it wrong and that water goes into the slab instead.

The five rules for the flange

  1. Recessed. The flange is set into the floor so it finishes flush. It never sits proud of the surface.
  2. Sealed to the pipe. The join between the flange and the riser is watertight.
  3. Fixed. The flange cannot move once it is set.
  4. Same size as the riser. A 100 mm pipe takes a 100 mm flange.
  5. Filleted. A bead of sealant is tooled where the flange meets the floor.

Puddle flange size: what decides it

The standard sizes the flange by the riser, not by what is on the shelf: the flange is the same nominal size as the riser it sits on, so a DN 100 riser takes a 100 mm puddle flange. Where the grate and the waste are different sizes, FORSPEC's reading is to match the flange to the pipe that passes through the floor at the flange. Check with the plumber before the flange is ordered.

At a floor waste the standard calls it a leak control flange. On site and in the shops it is a puddle flange. It is the same part.

The membrane on the flange

The membrane is bonded onto the flat of the flange, or onto the flat and down the leg. The standard gives no lap length, so follow the membrane's data sheet and the detail drawing. Keep the flange clear of bond breakers and of the wall and floor junction, so the two do not clash.

Where the membrane sits under a screed or tile bed, the flange has to drain the bed at membrane level, and the floor under the membrane falls to it at 1:100 or more.

Linear drains

With a channel drain, the membrane runs into the outlet without a break. If the channel has no built-in flange or upstand of 50 mm for the membrane to bond to, the membrane goes under the channel to a recessed flange below.

Who sets it?

The standards do not say which trade installs the flange. The plumbing standard covers the waste, the trap and the grate; it does not mention the flange at all.

FORSPEC's advice: the plumber sets the flange, and the waterproofer checks it is flush, fixed and sealed before the primer goes on. If it is not, stop and have it fixed.

Where to get one

A puddle flange is a plumbing fitting, not a FORSPEC product. FORSPEC makes the membrane and primer that go over it, and the lap onto the flange follows the membrane's data sheet: find a FORSPEC stockist. The whole bathroom build-up is on the wet area system page. FORSPEC details B100, a bathroom on concrete, and B104, a bathroom on fibre-cement sheet, show the flange in a bathroom floor; EEL007, the exposed roof outlet, shows it on a roof.

The drawing

Detail drawing: Puddle flanges: what AS 3740 requires at the floor waste

Where this comes from

Standards are summarised in FORSPEC's own words as a guide. Read the standard itself and your project documents before you build.

General information, correct at the date shown. Not advice for your job.

Email thisNewsletter

Systems, products and drawings

● Your job next

Got a job this applies to?

Send the drawings or a few photos. FORSPEC comes back with the system, the details and the products for your job, within 6 business hours.

On site with FORSPEC

@forspec.pc on Instagram →

More news

All news →
● The FORSPEC Brief · monthly

The month in waterproofing. In one email.

Code and standards changes, new products, new test reports and jobs from site. Once a month. No sales emails.

Pressing Sign me up asks us to email you The FORSPEC Brief, once a month. Unsubscribe in one click. We use your address only to send this newsletter.

Send us your job →☎